Industrial Cable

PV Cable

Walsin Lihwa PV cables have EN, UL, and S-JET certifications. PV cables are always used under high temperatures and must be resistant to heat, humidity, and sunlight. The UL, for example, requires USE-2 cables and PV cables stand for temperature higher than 90°C in a humid environment. PV cables are installed outdoors and also must pass a 720-hour weatherproof test as well as a -40°C low-temperature resistance test. The structure of PV cables is relatively simple and uncertified PV cables cannot reach the product life expectancy. Replacing uncertified PV cables is very costly and troublesome; on the other hand, certificated PV cables save maintenance costs significantly to enable more cost-efficient solar power generation.

Specifications

Conductor Overall diameter (Approx.) Maximum conductor resistance (20℃) AC test voltage Insulation resistance (15℃)
Size Construction Outerside diameter (Approx.)
mm2 no./mm mm mm Ω/km kW/min MΩ-km
1.5 28/0.25 1.57 5.72 13.7 3.0/1 1230
2.5 48/0.25 2.02 6.17 8.21 3.0/1 1040
4 80/0.25 2.59 6.74 5.09 3.0/1 870
6 119/0.25 3.57 8.52 3.39 3.5/1 850
10 126/0.32 4.71 9.66 1.95 3.5/1 690
16 203/0.32 5.97 10.92 1.24 3.5/1 570
25 315/0.32 7.44 12.39 0.795 3.5/1 470
35 437/0.32 8.9 14.9 0.565 4.0/1 510
50 608/0.32 10.45 16.45 0.393 4.0/1 450
70 437/0.45 12.5 18.5 0.277 4.0/1 380
95 608/0.45 14.7 20.7 0.21 4.0/1 330