Industrial Cable

PV Cable

Walsin Lihwa PV cables have EN, UL, and S-JET certifications. PV cables are always used under high temperatures and must be resistant to heat, humidity, and sunlight. The UL, for example, requires USE-2 cables and PV cables stand for temperature higher than 90°C in a humid environment. PV cables are installed outdoors and also must pass a 720-hour weatherproof test as well as a -40°C low-temperature resistance test. The structure of PV cables is relatively simple and uncertified PV cables cannot reach the product life expectancy. Replacing uncertified PV cables is very costly and troublesome; on the other hand, certificated PV cables save maintenance costs significantly to enable more cost-efficient solar power generation.

Specifications

UL 1000 and 2000V PV Wires

Conductor Overall diameter (Approx.) Maximum conductor resistance (20℃) AC test voltage Insulation resistance (15℃)
Size Construction Outerside diameter (Approx.)
mm2 no./mm mm mm Ω/km kW/min MΩ-km
1.5 28/0.25 1.57 6.52 13.7 6.0/1 1470
2.5 48/0.25 2.02 6.97 8.21 6.0/1 1260
4 80/0.25 2.59 7.54 5.09 6.0/1 1070
6 119/0.25 3.57 8.7 3.39 7.5/1 930
10 126/0.32 4.71 10.16 1.95 7.5/1 770
16 203/0.32 5.97 11.42 1.24 7.5/1 640
25 315/0.32 7.44 12.89 0.795 7.5/1 530
35 437/0.32 8.9 15.35 0.565 9.0/1 560
50 608/0.32 10.45 16.9 0.393 9.0/1 490
70 437/0.45 12.5 18.95 0.277 9.0/1 420
95 608/0.45 14.7 21.15 0.21 9.0/1 370
120 777/0.45 16.66 24.96 0.164 10.0/1 420
240 1517/0.45 23.31 31.61 0.0817 10.0/1 310